AWG to mm²: conversion table and how the gauge works

AWG sizes convert to mm² by calculation, because the American Wire Gauge is defined by two diameters and a fixed ratio between neighbouring sizes. AWG 20 is 0.518 mm², AWG 18 is 0.823 mm² and AWG 16 is 1.31 mm². The table lists the common sizes with the next larger metric cross-section.

As of 3 min read

Large-diameter high-current power cables with crimped lugs and heat-shrink sleeving
Contents
  1. Conversion table AWG 30 to 4/0
  2. How the gauge is defined
  3. Three rules of thumb
  4. Reading the table correctly
  5. On your drawing
  6. Sources

Conversion table AWG 30 to 4/0

AWG sizes in millimetres and square millimetres
AWGDiameter (mm)Cross-section (mm²)Next larger IEC 60228 size (mm²)
300.2550.0509–
280.3210.0810–
260.4050.129–
240.5110.205–
220.6440.326–
200.8120.5180.75
181.020.8231
161.291.311.5
141.632.082.5
122.053.314
102.595.266
83.268.3710
64.1213.316
45.1921.225
26.5433.635
1/08.2553.570
2/09.2767.470
3/010.485.095
4/011.7107120
Diameter and cross-section of a solid round conductor, calculated from the AWG definition and rounded to three significant figures. IEC 60228 starts at 0.5 mm²; smaller sizes are marked with a dash.

How the gauge is defined

Two sizes fix the gauge: No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch in diameter. The 38 sizes in between follow a geometric progression, so each step changes the diameter by the 39th root of 92, a factor of about 1.1229. The higher the number, the thinner the wire.

That gives a formula for any size n: d = 0.127 mm × 92^((36 − n) / 39), with 1 inch = 25.4 mm. For the sizes 1/0 to 4/0, n is 0, −1, −2 and −3. The cross-section follows from A = π × d² / 4.

The definition is set out in the Copper Wire Tables of the US National Bureau of Standards (Handbook 100) and is maintained today as ASTM B258.

Three rules of thumb

  • Three gauge numbers double or halve the cross-section: AWG 17 has about twice the cross-section of AWG 20.
  • Six gauge numbers double or halve the diameter.
  • Ten gauge numbers multiply or divide the cross-section by about ten: AWG 10 has about ten times the cross-section of AWG 20.

All three are approximations given in the NBS Copper Wire Tables. They follow from the ratio between sizes, whose cube is very close to 2.

Reading the table correctly

  • The diameter is that of a solid conductor. A stranded conductor of the same gauge has a larger outer diameter because of the gaps between the strands.
  • AWG and metric sizes rarely match. The next larger metric size carries more copper than the AWG size, but it may fall outside the wire range of the crimp contact.
  • Whether a metric wire can replace an AWG wire depends on current, voltage drop, temperature, the wire range of the crimp contact and the insulation diameter. That decision belongs on the drawing.
  • IEC 60228 (edition 4.0, 2023) sets the nominal cross-sections of conductors in power cables and cords from 0.5 mm² upwards. For thinner conductors, use the cross-section given in the cable's data sheet.

On your drawing

Give each wire one size in one system, preferably the one used in the data sheet of its crimp contact. If you list both AWG and mm², state which value governs. The enquiry checklist shows where the size belongs in the wire list.

Sources

  1. Copper Wire Tables, Handbook 100, section 2 (external page)National Bureau of Standards (today NIST) · 1966
  2. ASTM B258-18, Standard nominal diameters and cross-sectional areas of AWG sizes (external page)ASTM International
  3. IEC 60228:2023, Conductors of insulated cables (external page)International Electrotechnical Commission · Edition 4.0