Conversion table AWG 30 to 4/0
| AWG | Diameter (mm) | Cross-section (mm²) | Next larger IEC 60228 size (mm²) |
|---|---|---|---|
| 30 | 0.255 | 0.0509 | – |
| 28 | 0.321 | 0.0810 | – |
| 26 | 0.405 | 0.129 | – |
| 24 | 0.511 | 0.205 | – |
| 22 | 0.644 | 0.326 | – |
| 20 | 0.812 | 0.518 | 0.75 |
| 18 | 1.02 | 0.823 | 1 |
| 16 | 1.29 | 1.31 | 1.5 |
| 14 | 1.63 | 2.08 | 2.5 |
| 12 | 2.05 | 3.31 | 4 |
| 10 | 2.59 | 5.26 | 6 |
| 8 | 3.26 | 8.37 | 10 |
| 6 | 4.12 | 13.3 | 16 |
| 4 | 5.19 | 21.2 | 25 |
| 2 | 6.54 | 33.6 | 35 |
| 1/0 | 8.25 | 53.5 | 70 |
| 2/0 | 9.27 | 67.4 | 70 |
| 3/0 | 10.4 | 85.0 | 95 |
| 4/0 | 11.7 | 107 | 120 |
How the gauge is defined
Two sizes fix the gauge: No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch in diameter. The 38 sizes in between follow a geometric progression, so each step changes the diameter by the 39th root of 92, a factor of about 1.1229. The higher the number, the thinner the wire.
That gives a formula for any size n: d = 0.127 mm × 92^((36 − n) / 39), with 1 inch = 25.4 mm. For the sizes 1/0 to 4/0, n is 0, −1, −2 and −3. The cross-section follows from A = π × d² / 4.
The definition is set out in the Copper Wire Tables of the US National Bureau of Standards (Handbook 100) and is maintained today as ASTM B258.
Three rules of thumb
- Three gauge numbers double or halve the cross-section: AWG 17 has about twice the cross-section of AWG 20.
- Six gauge numbers double or halve the diameter.
- Ten gauge numbers multiply or divide the cross-section by about ten: AWG 10 has about ten times the cross-section of AWG 20.
All three are approximations given in the NBS Copper Wire Tables. They follow from the ratio between sizes, whose cube is very close to 2.
Reading the table correctly
- The diameter is that of a solid conductor. A stranded conductor of the same gauge has a larger outer diameter because of the gaps between the strands.
- AWG and metric sizes rarely match. The next larger metric size carries more copper than the AWG size, but it may fall outside the wire range of the crimp contact.
- Whether a metric wire can replace an AWG wire depends on current, voltage drop, temperature, the wire range of the crimp contact and the insulation diameter. That decision belongs on the drawing.
- IEC 60228 (edition 4.0, 2023) sets the nominal cross-sections of conductors in power cables and cords from 0.5 mm² upwards. For thinner conductors, use the cross-section given in the cable's data sheet.
On your drawing
Give each wire one size in one system, preferably the one used in the data sheet of its crimp contact. If you list both AWG and mm², state which value governs. The enquiry checklist shows where the size belongs in the wire list.